Systematic integration of overcurrent protection, power distribution and signalling on one board

SVS18-10-C10 数据手册

 浏览型号SVS18-10-C10的Datasheet PDF文件第2页浏览型号SVS18-10-C10的Datasheet PDF文件第3页浏览型号SVS18-10-C10的Datasheet PDF文件第4页浏览型号SVS18-10-C10的Datasheet PDF文件第5页浏览型号SVS18-10-C10的Datasheet PDF文件第6页 
Power Distribution System SVS18  
Description  
The power distribution system SVS18 optimises the DC 24 V distribution  
in automation and process control, in the production area of the  
chemical industry and in power plants. The power distribution system  
SVS18 DIN rail mounting distributes all voltage potentials supplied  
by a 24 V power supply (SMPS) onto 10 ways F1 to F10 (arranged  
from right to left). The system offers 2 integral redundancy diodes in  
each protected load output and selectively protects the connected  
loads such as controls, transformers, actuators, magnetic yoke sub-  
assemblies, bus modules etc. by means of the circuit breaker fitted.  
With a max. total current of 25 A and a typical load current of 3 A per  
way (max. 6 A in limited continuous duty) the SVS18 provides ease  
of distribution and sub-distribution in short-circuit-limited DC 24 V  
applications. All auxiliary contacts (make contacts) of the plugged-in  
circuit breakers are connected in series and allow group signalling in  
accordance with the closed-circuit principle. The 10 protected »L+«  
load outputs with 2 redundancy diodes per way significantly reduce  
the otherwise standard wiring time. All terminals of the DC 24 V  
supply, load outputs with 0V return conductor as well as the signalling  
terminals are screwless spring-loaded terminals.  
Technical data (T  
= 25 °C, U = DC 24 V)  
B
amb  
Application  
Suitable for the following E-T-A circuit breaker types:  
Modular power distribution system for short circuit current limited  
DC 24 V – applications.  
electronic circuit breaker  
ESS20-003-DC24V-  
max. 6A  
ESX10-103-DC24V-  
max. 6A  
Use with switch-mode power supply, e.g. type Quint DC 24 V / 20 A  
(manufactured by Phoenix Contact)  
electronic circuit protector  
Supply  
Rated voltage:  
DC 24 V (18...30 V), 2 supply potentials  
L1+ and L2+ possible  
Features and benefits  
Caution: L1+ and L2+ are bridged when  
delivered  
l
Systematic integration of overcurrent protection,  
power distribution and signalling on one board  
Power distribution and selective protection of DC 24 V load  
circuits fed by a single power supply (L1+ and L2+ are bridged)  
or by two separate power supplies (L1+, L2+)  
Clear distribution concept, two each redundancy diodes (typically  
1.5 A, max. 3 A per diode) connected in parallel integral in each  
load output  
Terminal block for group signalling (make contacts)  
Profitability through significant reduction of wiring time  
Reduced time and expenses for planning, design and installation  
Ease of maintenance, diagnosis and system extension  
Total current:  
max. 25 A, continuously  
DC 24 V (+) = X21 L1+/L1+  
DC 24 V (+) = X21 L2+/L2+  
DC 24 V (-) = X21 L-/L-/L-  
L1+: supply potential for F1/F3/F5/F7  
L2+: supply potential for F2/F4/F6/F8/F9/F10  
L-: 0 V return conductor for L1+ and L2+  
l
l
l
l
l
l
Terminals  
screwless plug-in terminal block, 7-pole  
max. cable cross section 0.75...10 mm2  
F-positions  
10 slots F1 to F10 for electronic circuit breakers,  
prepared for types ESS20-003, ESX10-103:  
placed from right (F1) to left (F10)  
Ordering information  
Type  
Input  
F1, F3, F5, F7:  
input connected to 24 V-voltage L1+  
F2, F4, F6, F8, F9, F10:  
SVS18 power distribution system for ESS20-003, ESX10-103  
l
For short circuit current limited DC 24  
V-applications  
input connected to 24 V-voltage L2+  
l
l
Max. 25 A cont. load  
Output L1+  
Output L2+  
F1, F3, F5, F7:  
Integral group signalling terminals X31,  
DC 24 V / max. 0.5 A , have to be protected separately  
Incl. 1 isolated bridge for terminal L1 and L2  
pushed in upon receipt  
Incl. 10 isolated bridges for load outputs, parallel  
connection of diodes Dx.1 and Dx.2, pushed in upon  
receipt  
Accessories: jumpers SB-11-P1-01-1-1A  
(for free slots), order separately  
Version, max. number of circuit breakers on  
the power distribution system  
Output via redundancy diodes  
to X1/L1, X3/L1, X5/L1, X7/L1  
(terminals 1+ , 2+ each)  
l
l
6
F2, F4, F6, F8, F9, F10:  
Output via redundancy diodes  
to X2/L2, X4/L2, X6/L2, X8/L2, X9/L2, X10/L2  
(terminals 1+ , 2+ each)  
l
Please plug jumper SB-11-P1-01-1-1A into  
free slots (to be ordered separately, see  
accessories)  
10 circuit breakers (F1...F10)  
Caution:  
Fitted version, load output and signalling terminals  
C10 standard: completed fitted with push-in-terminals  
(max. 2.5 mm², without wire end ferrule  
When using an electronic circuit breaker rated > 3 A, the  
redundancy diodes have to be connected in parallel. The  
jumper for connecting the diodes in parallel has to be  
plugged in.  
SVS18 - 10 -C10 ordering example  
Accessory: jumper, see Accessories  
1646  
www.e-t-a.de  
1

与SVS18-10-C10相关器件

型号 品牌 描述 获取价格 数据表
SVS20 ETAL Systematic integration of protection and distribution functions

获取价格

SVS20-08-B10-K01-SB01 ETAL Systematic integration of protection and distribution functions

获取价格

SVS20N60KD2 SILAN TO-262-3L

获取价格

SVS20N60P7D2 SILAN TO-247-3L

获取价格

SVS20N60SD2 SILAN TO-263-2L

获取价格

SVS20N60TD2 SILAN TO-220-3L

获取价格