FEATURES
●Fitted devices: 1. NAMUR Sensors;
2. Mechanical Joints.
● Phase-angel and inverse control setting;
● Open circuit detection setting
● Operation Temperature:-25°C to +71°C
● Reliable Performance (MTBF>1,000,000 hours)
Isolating / Safety Switching Barrier
(Transistor Output)
——TSX01-EX Series
PART NUMBER SYSTEM
GENERAL DESCRIPTION
TS201-EX
This Isolation Switching Barrier can detect switch or approach
switch’s status in locations where hazardous exists; isolate, transmit
and output it to safe area. Input and output can be set to inverse
control. Approach switch open circuit detection function. Isolation
between Input/ Output/Power source.
Safety barrier mark
Transistor output
Channel number
Signal style
Product seriers
PRODUCT PROGRAM
Input(Power)
Voltage(VDC)
Output(Hazardous end)
Output
(Safe end)
Channel
numbers
Part number
Voltage
Typ.
Short Circuit
Current
Typ.
Range
TS101
TS201
1
2
1
2
24
18-36
8VDC
About 8 mA
Transistor Output
TS101-EX
TS201-EX
ELECTRICAL SPECIFICATIONS
Operation voltage
18-36VDC
Common parameter
Hazardous Area
Input frequency
Power indicating
Input Signal
About 2.4W
LED light (green) ON when operating
Switch status of NAMUR sensor, mechanical joint etc
Distribution voltage
Short circuit current
About 8V (Open status)
About 8mA
Input switching frequency
Open circuit threshold current
Switching threshold
Output signal
≤5kHz
≤0.1mA
Typ:1.55mA (hysteresis:0.2mA)
Transistor output (Passive pulse)
≤40VDC
External source
Safe Area
Driving capability
≤40mA(Build-in short circuit protection)
High Level: Vcc ; Low Level: ≤2.5VDC
High Level: Vcc-2.5V ; Low Level: ≤0.5VDC
Transistor collector
Transistor Emitter
TRANSMISSION SPECIFICATIONS
Input loop current > 2.1mA, transistor output open, channel indicator light (red) ON.
Under phase-angel control (K2 K3 OFF )
Input loop current < 1.2mA, transistor output close, channel indicator light (red) OFF.
Input loop current > 2.1mA, transistor output close, channel indicator light (red) OFF.
Input loop current < 1.2mA, transistor output open, channel indicator light (red) ON.
Input loop current < 0.05mA, open circuit alarm, channel red indicator light (yellow) ON.
Under inverse control (K2 K3 ON )
When connected with NAMUR sensor
When connected with common contact joint To achieve open circuit detection function, a 10KΩ resistor must be connected to the switch in
switch parallel.
Note: K2 is setup channel1 to be reverse or not ,K3 is setup channel2 to be reverse or not.
The copyright and authority for the interpretation of the products are reserved by MORNSUN
TSX01-EX
2013.07.01-A/4
Page 1 of 3