5秒后页面跳转
ESX10-S PDF预览

ESX10-S

更新时间: 2022-12-29 19:54:22
品牌 Logo 应用领域
ETAL /
页数 文件大小 规格书
6页 303K
描述
Selective load protection, electronic trip curve

ESX10-S 数据手册

 浏览型号ESX10-S的Datasheet PDF文件第2页浏览型号ESX10-S的Datasheet PDF文件第3页浏览型号ESX10-S的Datasheet PDF文件第4页浏览型号ESX10-S的Datasheet PDF文件第5页浏览型号ESX10-S的Datasheet PDF文件第6页 
Electronic circuit protector ESX10-Sxxx-DC24V-1A-10A  
Description  
The model ESX10-Sxxx extends our product group of electronic  
overcurrent protection devices for DC 24 V applications.  
At a width of only 12.5mm it provides selective protection for all DC  
24 V load circuits. This is achieved by a combination of active elec-  
tronic current limitation in the event of a short circuit and overload  
disconnection typically from 1.2 times rated current. The ESX10-S is  
a plug-in type and thus allows quick and easy installation for groups  
of devices with several circuits on the power distribution systems  
Module 17plus and SVSxx.  
DC 24 V switch-mode power supplies are widely used in automation  
today. In the event of an overload, however, they turn down the output  
voltage which is intended to power all connected loads. So if there is  
a failure in a single load of the system, the supply voltage will break  
down also in all other load circuits. Not only does this frequently cause  
undefined fault conditions, but it can even lead to machine stoppages  
or system downtimes.  
ESX10-S  
Technical data (T  
= 25 °C, U = DC 24 V)  
B
amb  
This is exactly where the ESX10-S comes in by responding to the  
overload conditions faster than the switch-mode power supply. The  
max. possible overcurrent is limited to typically 1.4 times rated current  
(see table 1). This allows switching on capacitive loads of up to 20,000  
µF, but a disconnection will only be effected in the event of an over-  
load or short circuit. For adjustment to the load conditions the current  
rating can be selected by means of a rotary switch from 1A to 10A.  
Status and failure indication is by means of a multi-coloured LED, an  
integral short circuit proof status output (single or group alarms) or via  
a potential-free relay contact (change-over contact). Remote actua-  
tion is possible via a remote reset signal. The manual ON/OFF switch  
on the device itself allows start-up of certain individual load circuits.  
As soon as the ESX10-S detects overload or short circuit in its load  
circuit, it blocks the load output transistor and disconnects the current  
flow in the faulty circuit. After remedy of the failure, the load output of  
the ESX10-S is re-activated by an electronic reset signal or manually  
by actuating the ON/OFF switch on the device.  
Operating data  
Operating voltage UB  
Current ratings IN  
DC 24 V (18...32 V)  
adjustable ratings:  
1 A through 10 A in 1 A steps  
Standby current I0  
in ON condition:  
typically 25 mA with version -103/-115/-125  
typically 20 mA with version -114/-117/-  
124/-127  
multicoloured LED:  
green:  
- load circuit connected  
Visual status  
indication  
flashing (green/yellow):  
- load current warning limit reached 80%  
yellow:  
- overload or short circuit until  
disconnection  
US patent number: US 6,490,141 B2  
red:  
- after disconnection due to overload,  
short circuit or temperature  
- after undervoltage disconnection in ON  
condition of operating voltage with auto-  
matic reset  
4
Features and Benefits  
l
Selective load protection, electronic trip curve  
All types of loads can be connected (DC 24 V motors upon  
request)  
Active current limitation when switching on capacitive loads  
up to min. 20,000 µF and in case of overload/short circuit  
Whole-number adjustable current ratings from 1A to 10 A  
by means of rotary switch  
l
flashing (red/OFF):  
- upon changed rating adjustment  
l
OFF:  
- devices switched off via  
ON/OFF switch  
- no operating voltage with ON/OFF  
l
l
switch in ON condition  
Reliable overload disconnection typically from 1.2 x IN even with  
long load lines or small cable cross sections  
Manuel ON/OFF switch (S1)  
Clear status indication by means of LED, electronic status output  
Load circuit  
l
Load output  
power MOSFET switching output  
(plus switching)  
l
SF or signal output F (potential-free auxiliary contact)  
Electronic reset input RE, control input IN  
Integral fail-safe-element  
Width per channel only 12.5 mm  
Plug-in type mounting on power distribution system Module  
17plus and SVSxx.  
Load current  
warning limit (ILimit  
hysteresis  
typically 0.8 x IN  
l
)
l
typically 5%  
l
Overload disconnection typically 1.2 x IN (1.05...1.35 x IN)  
l
(IOL  
)
(see time/current characteristic)  
Short circuit current (ISC  
)
active current limitation with ISC  
typically 2.5 x IN , 1 A  
=
typically 1.4 x IN, 2 A -10 A  
(see time/current characteristic)  
Approvals  
Trip times  
at overload disconnection (IOL) = typ. 3 s  
at short circuit current (ISC) = typically 0.1 s  
(see time/current characteristic)  
Authority  
UL  
Standard  
Rated voltage  
DC 24 V  
Current ratings  
1...10 A  
UL 2367  
Temperature  
internal temperature monitoring with  
monitoring electronic disconnection  
UL  
UL 508  
C22.2 No 14  
DC 24 V  
1...10 A  
disconnection  
hysteresis  
typically +100 °C  
typically 10 °C  
Operating voltage  
monitoring with regard  
to low voltage  
OFF at typically UB < 16.0 V  
ON at typically UB> 17.5 V  
with automatic ON and OFF switching  
1646  
www.e-t-a.de  
1

与ESX10-S相关器件

型号 品牌 描述 获取价格 数据表
ESX10-S103-DC24V-10A ETAL Selective load protection, electronic trip curve

获取价格

ESX10-S103-DC24V-1A ETAL Selective load protection, electronic trip curve

获取价格

ESX10-S103-DC24V-2A ETAL Selective load protection, electronic trip curve

获取价格

ESX10-S103-DC24V-3A ETAL Selective load protection, electronic trip curve

获取价格

ESX10-S103-DC24V-4A ETAL Selective load protection, electronic trip curve

获取价格

ESX10-S103-DC24V-5A ETAL Selective load protection, electronic trip curve

获取价格