Magnetic and Hydraulic-Magnetic Circuit Breaker 8335-...
Description
Single and multipole magnetic circuit breakers with trip-free mechanism
and toggle actuation. A choice of fast magnetic or hydraulically dela-
yed switching characteristics (S-type MO or HM CBE to EN 60934)
ensures suitability for a wide range of applications. Industry standard
dimensions and panel mounting. Options include auxiliary changeover
contacts. Low temperature sensitivity at rated load.
Approved to CBE standard EN 60934 (IEC 60934): S-type HM CBE.
Typical applications
Communications systems, power supplies, switchgear and controlgear
industrial process measurement and control.
8335-...
1-pole
2-pole
Standard current ratings and typical internal resistance values
Technical data
Current
rating (A)
Internal resistance (Ω) per pole 10%
For further details please see chapter: Technical Information
K1, M1, T1
K2, M2, T2
Voltage rating
Current ratings
Auxiliary circuit
3 AC 415 V; AC 240 V (50/60 Hz); DC 80 V
1...50 A 1- and multipole
1
2
3
4
5
6
1.04
1.03
0.22
0.22
AC 250 V
DC 80 V
5 A
0,5 A
0.11
0,11
0.06
0.06
Typical life
3 AC 415 V,
AC 240 V: 1...30 A
0.04
0.04
6,000 operations at 1 x IN, inductive
10,000 operations at 1 x IN, resistive
10,000 operations at 1 x IN, inductive
10,000 operations at 1 x IN, resistive
0.03
0.03
8
10
0.02
< 0.02
0.02
< 0.02
DC 80 V:
1...50 A
12
15
16
20
24
25
30
35
40
45
50
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.01
< 0.01
< 0.01
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
-
Ambient temperature
-40 °C...85 °C
4
Insulation co-ordination
(IEC 60664)
rated impulse
withstand voltage
2.5 kV
pollution
degree
2
reinforced insulation in operating area
Dielectric strength
operating area
Line to Load
pole to pole (2- and 3-pole) test voltage AC 1,500 V
main to auxiliary circuit test voltage AC 1,500 V
test voltage AC 3,000 V
test voltage AC 1,500 V
-
Insulation resistance
> 100 MΩ (DC 500 V)
1,500 A (AC, DC)
-
Interrupting capacity Icn
Interrupting capacity (UL 1077)
Standard Ignition
protected
-
(UL 1500)
DC 80 V
DC 80 V
DC 65 V
1- + 2-pole
1- + 2-pole
1- + 2-pole
1...30 A
1...50 A
1...50 A
3,000 A
1,500 A
3,000 A
U1a
U1a
U1a
---
---
U1a
Approvals
DC 32 V
AC 250 V 1- + 2-pole
1- + 2-pole
1...50 A
1...30 A
5,000 A
5,000 A
3,000 A
1,000 A
3,000 A
2,000 A
5,000 A
1,000 A
U3
C1A
U1a
U1a
U1a
U3
U3
---
U1a
---
Authority
Voltage ratings
Current ratings
1)
VDE (EN 60934) DC 80 V
AC 240 V
1...50 A
1...30 A
1...30 A 1- and multipole
AC 250 V 1- + 2-pole
AC125/250 V
AC125/250 V
3 AC 250 V
3 AC 250 V
1...50 A
1...30 A
1...50 A
1...30 A
1...50 A
3 AC 415 V
2-poe
U1a
1)
1)
UL 1077
DC 80 V
AC 250 V
AC 125 V / 250 V
1...50 A
1...50 A
1...50 A 1- and multipole
2-pole
3-pole
3-pole
---
---
---
U1a
U3
Interrupting capacity (UL 489A) 1,500 A
Ignition
DC 65 V
DC 32 V (ABYC)
AC 125 V/250 V (ABYC) 1...30 A 2-pole
AC 250 V (ABYC)
1...50 A 1- and 2-pole
1...50 A 1- and 2-pole
protected
(UL 10 77 +
UL 1500)
Degree of protection
(IEC 60529/DIN 40050)
operating area IP40
terminal area IP00
1...30 A 1-pole
Vibration
all mounting positions: 10 g (57-2000 Hz)
0.76 mm (10-57 Hz) at 0.9 x IN
to IEC 60068-2-6, test Fc
1)
1)
UL 489A
CCC
DC 80 V
1...50 A 1- and 2-pole
DC 80 V
AC 240 V/415 V
1...50 A 1- and 2-pole
1...30 A 1...3-pole
10 frequency cycles/axis
Shock
all shock directions
100 g (11 ms) at 0.8 x IN
to IEC 60068-2-27, test Ea
1) Depending on the circuit breaker configuration
Corrosion
Humidity
Mass
96 hours at 5% salt mist,
to IEC 60068-2-11, test Ka
240 hours at 95 % RH
to IEC 60068-2-78, test Cab
approx. 65 g per pole
2014/15
www.e-t-a.de
4 - 1