FUSES / SICHERUNGEN
FSQ 5 ꢀ 20
Non resettable fuses
Miniature Fuses
Type FSQ 5 ꢀ 20
quick-acting F
Glass tube
100'000
UL 198 G
UL 248-14
Istwertalues
test v
10'000
1'000
100
10
50
75
100
Standards
UL 248-14
CSA C22.2 No. 248.14
1
Approvals
UL
CSA
0,1
0,01
Pre-arcing time/current
characteristic (at Ta 23 °C)
n · In
0,001
Rated
current In
3
6
7
8
9
10
15
1
2
4
5
1,1 · In* 1,35 · In 2 · In
Multiple of rated current In
min.
4 h
max.
1 h
max.
400 mA– 3,5A
120 s
* Non fusing current Inf
Order No. / Rated current In
Rated voltage Un /
Breaking capacity / Voltage drop /
at / bei In
Sustained
power dissipation /
Pre-arcing
l2t
Approvals
at / bei 1,1 In
at / bei 10 · In
n
typ.
mV
170
typ.
W
typ.
A2s
0034.3951
0034.3952
0034.3953
0034.3954
0034.3955
0034.3956
0034.3957
0034.3958
0034.3959
0034.3960
0034.3961
0034.3962
0034.3963
0034.3964
0034.3965
0034.3966
0034.3967
0034.3968
0034.3969
400 mA / 250 V
500 mA / 250 V
600 mA / 250 V
700 mA / 250 V
750 mA / 250 V
800 mA / 250 V
0,1
0,1
0,1
0,2
0,2
0,2
0,2
0,2
0,2
0,3
0,3
0,3
0,3
0,3
0,4
0,5
0,5
0,5
0,5
8,2 · 10–1
2,11 · 10–1
2,58 · 10–1
4,17 · 10–1
6 · 10–1
6,62 · 10–1
1,15
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
10 000 A / 125 V AC,
p.f. / cos ꢀ 0,7-0,8
140
150
150
150
140
120
110
110
110
110
100
100
100
100
100
100
100
90
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
35 A / 250 V AC,
p.f. / cos ꢀ 0,7-0,8
1
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
A / 250 V
1,2
1,25
1,5
1,6
1,8
2
1,82
1,84
3,11
3,84
4,07
4,51
6,77
11,1
12,7
14,8
19,2
26,3
10 000 A / 125 V AC,
p.f. / cos ꢀ 0,7-0,8
2,25
2,5
2,8
3
100 A / 250 V AC,
p.f. / cos ꢀ 0,7-0,8
3,2
3,5
93
www.schurter.com